Model: UT-10-12/UT-10-24/UT-40-48/UT-40-200
● Remote signal definition (optional): NC-COM: Turn off, COM: Common point, NO-COM: Turn on
● Failure indication: Green; Normal; Red: Failed
●Response time (ta): 25ns
● Dimensions: 90*36*65mm
● Protection level: IP20
● Preposed fuse: 40Agl/gg
● Protection mode: +/PE, -/PE
● Flame retardant level: V0/red
● Installation method: 35mm DIN rail installation
● Operating environment: Temperature -40~+85℃, relative humidity≤95%(25℃), height≤3km
Model |
UT-10-12 |
UT-10-24 |
UT-40-48 |
UT-40-200 |
Operating voltage (Un) |
12VDC |
24VDC |
48VDC |
200VDC |
Max. operating voltage |
24VDC |
30VDC |
85VDC |
320VD |
Nominal discharge current (In) |
5kA |
20kA |
||
Maximum flow capacity (Imax) |
10kA |
40kA |
||
Protection level (Up is In) |
≤100V |
≤150V |
≤350V |
≤1200V |
Access wire area |
≥4 mm2 |
≥6 mm2 |
||
Remote Signal Definition (Optional) |
NC-COM: turn off, COM: common point, NO-COM: turn on |
|||
Failure indication |
Green: Normal; Red: Failed |
|||
Response time (tA) |
25ns |
|||
Dimensions |
90*36*65mm |
|||
Protection level |
IP20 |
|||
Preposed fuse |
40AgL/gG |
|||
Protection mode |
+/PE, -/PE |
|||
Flame retardant level |
V0/red |
|||
Installation method |
35mm DIN rail installation |
|||
Operating environment |